KOY HAUKI    OMA HAMMASLÄÄKÄRI    ETELÄESPLANADI 22    00130 HELSINKI          Area of the sealed ductwork 46m2 .      Measured leakage before sealing 77 l/s = 1,67 l/s / m2 .     Measured leakage after sealing 9 l/s = 0,195 l/s / m2.

KOY HAUKI

OMA HAMMASLÄÄKÄRI

ETELÄESPLANADI 22

00130 HELSINKI

 

Area of the sealed ductwork 46m2.

Measured leakage before sealing 77 l/s = 1,67 l/s / m2.

Measured leakage after sealing 9 l/s = 0,195 l/s / m2.

  TAKSIAUTOILIJOIDEN   TOIMITALO    ASESEPÄNKUJA 2    00620 HELSINKI        Area of the sealed ductwork  83m2.    Measured leakage before sealing  103,9 l/s = 1,25 l/s /m2.   Measured leakage after sealing  21,4 l/s = 0,257 l/s /m2.

TAKSIAUTOILIJOIDEN TOIMITALO

ASESEPÄNKUJA 2

00620 HELSINKI

 

Area of the sealed ductwork 83m2.

Measured leakage before sealing 103,9 l/s = 1,25 l/s /m2.

Measured leakage after sealing 21,4 l/s = 0,257 l/s /m2.

  UNISPORT TÖÖLÖ    ILMARINKATU 1    00100 HELSINKI        Area of the sealed ductwork  70m2.    Measured leakage before sealing  142,2 l/s = 2,03 l/s /m2.   Measured leakage after sealing  10,7 l/s = 0,15 l/s /m2.

UNISPORT TÖÖLÖ

ILMARINKATU 1

00100 HELSINKI

 

Area of the sealed ductwork 70m2.

Measured leakage before sealing 142,2 l/s = 2,03 l/s /m2.

Measured leakage after sealing 10,7 l/s = 0,15 l/s /m2.

  SIMONMETSÄN PÄIVÄKOTI    RAATETIE 25    01350 VANTAA        Area of the sealed ductwork , supply, 110m2.    Measured leakage before sealing  157,4 l/s = 1,43 l/s /m2.   Measured leakage after sealing  25,1 l/s = 0,23 l/s /m2.       Area of the sealed ductwork , return, 87m2    Measured leakage before sealing  155,2 l/s = 1,78 l/s / m2.   Measured leakage after sealing  15 l/s = 0,17 l/s / m2.

SIMONMETSÄN PÄIVÄKOTI

RAATETIE 25

01350 VANTAA

 

Area of the sealed ductwork, supply, 110m2.

Measured leakage before sealing 157,4 l/s = 1,43 l/s /m2.

Measured leakage after sealing 25,1 l/s = 0,23 l/s /m2.

 

Area of the sealed ductwork, return, 87m2

Measured leakage before sealing 155,2 l/s = 1,78 l/s / m2.

Measured leakage after sealing 15 l/s = 0,17 l/s / m2.

  VANTAANKOSKEN PALOASEMA    MARTINKYLÄNTIE 3    01670 VANTAA        Area of the sealed ductwork, supply,  337m2.    Measured leakage before sealing  368,4 l/s = 1,09 l/s /m2.   Measured leakage after sealing  41,7 l/s = 0,12 l/s /m2.    Area of the sealed ductwork, return,   161,5m2.    Measured leakage before sealing  279,3 l/s = 1,73 l/s /m2.   Measured leakage after sealing  15 l/s = 0,18 l/s /m2.

VANTAANKOSKEN PALOASEMA

MARTINKYLÄNTIE 3

01670 VANTAA

 

Area of the sealed ductwork, supply, 337m2.

Measured leakage before sealing 368,4 l/s = 1,09 l/s /m2.

Measured leakage after sealing 41,7 l/s = 0,12 l/s /m2.

Area of the sealed ductwork, return, 161,5m2.

Measured leakage before sealing 279,3 l/s = 1,73 l/s /m2.